Technical conditions for the installation of a heat meter validity period. Is it profitable to install an individual heat meter in an apartment and how to do it right

Heat energy meter or heat meter- this is a device, according to the indications, which is charged for the received thermal energy.

Purpose of installation

By installing a meter, it becomes possible to control the cost of thermal energy, make decisions on the implementation of energy saving measures. After installing a heat meter, payments for heat, as a rule, are reduced, but the meter itself does not provide savings.

The reduction in costs is due to payment for the actually delivered heat, and not according to calculations based on the average monthly ambient temperature and the standard temperature in the apartment.

Thermal energy meters can be installed both in a separate apartment and in an apartment building.

A meter installed for one consumer is called individual, for several consumers - collective. As you know, from the course of general physics, the amount of heat is calculated by the formula Q \u003d m × (t1-t2).

To calculate the thermal energy, the values ​​\u200b\u200blook like this:

  • Q - The amount of heat;
  • m is the mass of water passing through the heat meter in one hour (water consumption);
  • t1 is the temperature in the supply pipeline;
  • t2 is the temperature in the return pipeline;

They also work on these 3 indicators. To measure the temperature, thermal sensors are used, which are installed in the return and supply pipelines. The difference in heat meters in the types of measurement of the amount of water.

Varieties: pros and cons

There are several types of heat meters:

  1. Tachometric. These are mechanical devices. The principle of their work is quite simple. The flow meter must be connected to the heat supply system of the house, and it will take into account the amount of coolant that has passed through it. An impeller is installed inside the flow meter, which rotates from the flow of water. As you know, the batteries in the apartment and the house are heated by hot water. For heating systems with very hard water, it is better not to use mechanical devices, The cost is relatively low.
  2. Ultrasonic. This type of counters has a large number of modifications. However, they all work on the same principle. It is installed on the supply or return pipe. As an example, the following type of installation: the emitter is installed after the battery, and the sensors are installed in front of the radiator. These meters are distinguished by a rather high accuracy class, while the price of such devices is quite acceptable and depends on the modification.
  3. Electromagnetic. This type can be classified as the most expensive. This is the price of great opportunity. It can be used to account for thermal energy both in closed heating systems and in open ones. It additionally allows you to take into account the water flow and temperature flow. All processes are automated, and calculation data is displayed on the screen.
  4. Vortex. They are able to measure not only water, but also steam. According to the principle of operation, they differ from other heating meters. The device is installed on a pipe between 2 nozzles.
  5. Radiator diffusers. Most often they are installed on heating radiators in apartments where there are several heating risers.

Device installation procedure: instructions


You need to do the following:

  1. Hold a meeting of all residents of the house and document the decision to install a heat meter, select a responsible person (draw up and sign a protocol).
  2. Send a letter to the heat supply organization in order to obtain technical specifications for the installation. It is important to consider that the place of installation of the heat meter will be the boundary of responsibility for the condition of the pipelines. Before the TCO metering station - after the apartment owners or the management company. The specifications will state:
    • installation location;
    • its technical characteristics;
    • diameters of pipelines on which the installation will be carried out;
  3. With received specifications it is necessary to contact the design organization for the preparation of project documentation. The project for the installation of a heat meter, as a rule, is typical, but requires adaptation to a specific installation site. Documentation can take up to two months to complete. The project must include:
    • A specific model of the heat meter (preliminarily agreed with the customer), corresponding to the received technical conditions.
    • Installation diagram.
    • Estimated documentation.
  4. The developed project must be approved by the organization which issued the specifications. The approval period is from 1 to 2 weeks, provided that the documentation was not sent for revision.
  5. It is necessary to purchase a meter specified in the project documentation. When buying, please note that the passport of the heat meter is with a valid stamp of the state verifier.
  6. Installation of a heat meter. The installation of heating meters is carried out only by specialists, and such work cannot be carried out on their own. It is necessary to contact a company that has all the necessary permits for the provision of services of this kind.
  7. For commissioning it is necessary to sign an agreement with the enterprise supplier of thermal energy. Although this step seems simple, it can take a long time. Before putting it into operation, it is necessarily sealed. The responsibility for the integrity of the seals during the entire period of operation lies with the owner.

During operation, it must be passed for state verification once every 4 years. This is done to verify correct operation. Also, in the non-heating season, it is necessary to clean the mechanical filter and replace the batteries.

The owner is obliged to properly operate the meter, in accordance with the technical requirements. Thus, the owner of the metering unit must sign a contract for the maintenance of metering devices with a service organization (for example, it can be an installation company, an energy supply organization, a management company).

Readings for calculations for the released heat are taken once a month on the dates specified in the contract. When taking readings, representatives of the heat supplier and the consumer are present. The recorded data are entered into the relevant act and confirmed by the signatures of both parties.

Calculation of heat energy consumption

The calculation for the received heat is made according to the amount of heat consumed for a certain period, at the price specified in the contract. For example, 50 Gcal were released per month at a price of 1,100 rubles per 1 Gcal, therefore, 55,000 rubles were payable.

Now you need to decompose the amount for all homeowners. To do this, it must be remembered that thermal energy is used not only for heating apartments, but also for non-residential premises.

Therefore, the area of ​​heated non-residential premises is evenly distributed in proportion to the living area for all owners.

For example, if the total area of ​​the house is 1200 m2 and the living area is 1000 m2, then for each meter of living space there is 0.2 m2 of non-residential area. Then add up the area of ​​​​the apartment and the area of ​​\u200b\u200bher share in the house property. The result is multiplied by the cost of heating one "square meter".

At whose expense and how much does it cost to install the device?


According to the Federal Law (as amended on July 18, 2011) dated November 23, 2009 No. 261-FZ, until July 1, 2012, owners of premises in apartment buildings are required to ensure the installation of heat energy meters.

Paragraph 12 of Article 13 of Federal Law No. 261-FZ establishes that in the event of non-fulfillment by the owners of premises in an apartment building, the obligation to ensure that such a house is equipped with a common house meter, used communal resource, the organization that supplies the house becomes the person obliged to ensure that the house is equipped with the indicated device appropriate community resource.

Price installation is quite expensive. But given the fact that the cost of the entire complex of works is decomposed into all homeowners, the numbers do not look terrifying.

So, to install a meter for a typical five-story building, you will have to pay about 400 thousand rubles.. After recalculating the cost of installation, according to square meters of living space, it turns out about 4 thousand rubles from the owner of an apartment of 50 m2. If such an amount is unbearable, then homeowners are entitled to installment plans for up to 5 years. True, you will have to pay interest on the loan at the level of the refinancing rate.

The payback period for installing heat meters is on average 3-4 years. If you additionally engage in phased energy saving, you can achieve savings of 30 - 40%.

Any buildings and apartments that are connected to the district heating network use heat to organize and maintain the optimum temperature for consumers. A device that organizes the control of the amount of energy is called a heat meter. Such a device must meet the requirements for heat metering units in accordance with the concluded agreement with representatives of the heating network. It can also control readings and parameters during the operation of heat carriers (water and steam circulating in heating devices) at consumers.

Rules for the organization of commercial metering of thermal energy

When using a heat meter under a contract, the consumer pays only for the amount of heat produced. This device is needed to save the amount of heat consumed and reduce fuel costs in accordance with the signed contract after the adoption of the act. Technical metering of thermal energy is the organization of control of power grid equipment necessary in a modern building.

The requirements for commercial heat metering units say that these are devices for organizing temperature and volume measurement of heat energy. According to the rules, they consist of a flow meter, inlet and outlet temperature sensors and an electronic calculator. Given the information on the mass of the flow, the consumer can determine the volume of water and steam that the equipment produces from the meter.

To organize the measurement of parameters, consumers can use the following formula: the mass of heat produced is equal to the volume of heat supplied through the flow meter, multiplied by the difference in temperature in the supply and return pipelines. This indicator is multiplied by the heat transfer coefficient, which characterizes the parameters of the equipment according to the operating contract.

The current technical conditions and the passport of the heat energy metering station determine the installation rules. For example, a heat meter must be included in the register of measuring instruments, like any other metrological device.

According to the technical specifications for organizing the installation of heat metering devices, flow meters are mounted on straight sections of the system, and temperature sensors are mounted on pipelines with a diameter of at least 70 mm with the inclusion of additional fittings (filters, ball valves, measuring pressure gauges and thermometers). Works are carried out by representatives of the heating network.

This set of heating system equipment is called a commercial metering unit according to the rules of the organization. Requirements for work on its installation are regulated in article 19 (Organization of commercial accounting of thermal energy, heat carrier of the Federal Law "On Heat Supply").

Installation of measuring equipment

According to the rules for installing heat meters, there are two ways to install measuring devices:

  1. Measurement of temperature and energy mass requires the organization of heat meters on each heat carrier. To get the total mass heat consumption for an apartment, the consumer needs to add data on all equipment in the reporting period.
  2. The organization of one metering device for heat consumption at the riser and temperature sensors is carried out on each heat carrier at consumers. At the same time, the scope of work on reprogramming is determined by representatives of the heating network. They also add data for each pipeline to get the total consumption by consumers.

Only single-pipe horizontal systems allow measurement with one heat meter. However, such devices are equipped only in industrial and industrial buildings. Therefore, an effective solution to the problem, which does not require significant capital investments and reconstruction of the premises, is the installation of commercial temperature measuring instruments.

Requirements for heat energy meters

According to the specifications, commercial measuring devices are mounted on pipes in specially designated areas. It is necessary to provide access to heat meters and equipment for accounting and control.

The requirements for the installation of metering devices are based on the need to recognize them as commercial equipment that monitors the heating system for several years. These include:

  • mandatory registration in the register of measuring devices;
  • organization of protection against unauthorized intervention in the operation of equipment in the reporting period;
  • the minimum number of recorded parameters for calculating energy volume measurements;
  • autonomous power sources that will last at least 5-6 years;
  • compliance with the standard calibration time period (depending on the type of meter).

The choice of the metering unit is carried out according to the characteristics of the coolant. Limits of permissible relative errors for meters, registration of operating time and downtime are regulated by the project. These parameters are determined by the requirements of the organization of commercial metering units.

Engineering equipment is selected as follows:

  • consumers are determined by the type of equipment included in the register, or those devices that have passed the state metrological certification;
  • for the measuring device, it is necessary to provide comfortable rooms to which unauthorized access is impossible. You also need reliable waterproofing and affordable lighting, in which it is easy to read meters.

When developing a project for a metering station, it is necessary to determine the technical data and take into account the requirements and recommendations for the organization and assembly of measuring instruments, pipe fittings, pollution protection equipment and connecting elements. Installation must be carried out under the contract, then the act is accepted by the head of the heating network. Detailed information can be found in the manufacturer's data sheets and regulatory documents for the equipment. Also, the operating agreement defines the forms of reporting statements of meter readings.

The beginning of the organization of the work of the measuring control device is carried out by the representative of the heat supply together with the consumer after the acceptance of the device. Two identical copies of the certificate of admission to operation of the heat energy metering unit are drawn up, while one copy is provided to the consumer, the other to the heating network employee. The act of commissioning a heat metering unit for consumers is approved by the head of the heating network within a few days.

The quality management system is certified for compliance

requirements of GOST RV 15..

Statement of Conformity No. BP. ZK.22/.

288" height="34" style="vertical-align:top">

_________________________ № _______________________

To No. ___________________ dated _______________________

Head

TECHNICAL CONDITIONSNo. _____________ dated "_____" ______ 200__

FOR THE ORGANIZATION OF THERMAL ENERGY ACCOUNTING

(place of installation of the metering unit, type of attached object)

_____________________________________________________________________________________________________________________

Qmax= Gcal/hour

_____________________________________________________________________________________________________________________

The connection of the heat load is carried out in accordance with:

________________________________________________________________________________________

(technical conditions "Electronics" No. ______________ dated "______" ____________ 200___)

DESIGN OF THE HEAT METERING UNIT

1. The following documents are required for designing:

1.1. "Technical conditions for connecting the heat load of the consumer" to the heat networks issued by Electronics, indicating the design heat loads by type of heat consumption (for newly designed facilities).

1.2. Existing power supply contract, "Technical conditions for the reconstruction of the heat point" (for subscribers who are scheduled for reconstruction with the replacement of equipment) issued by Electronics.

1.3. Existing power supply contract, "Technical conditions for connection of additional heat load (objects) to an existing heating point", issued by Electronics, indicating the design heat loads by types of heat consumption.

1.4. Temperature and hydraulic schedule of coolant parameters, agreed with the Consumer and the power supply organization.

2. The project must provide for:

2.1. Compliance of the Project with the requirements of the "Rules for the technical operation of thermal power plants"; "Rules for accounting for thermal energy and coolant".

2.2. Schedule of heat consumption by day (heating and summer periods), certified by the consumer of thermal energy.

2.3.Functional scheme for measuring coolant flow, temperature, pressure and thermal energy.

2.4. Schemes of installation of flow sensors, temperature on pipelines, observing the lengths of straight sections indicated in the passport data of the heat energy meter.

2.5. Schemes of communication lines, power supply circuits from flow sensors, temperatures, pressures to the heat calculator.

Communication lines and power circuits are laid in separate electrical steel pipes or metal hoses. The types of cables used in the circuit must comply with those specified in the technical requirements of the manufacturer of the heat meter.

2.6. Mounting of the heat meter, power supplies, adapter, power supply units in a separate, sealed metal shield, excluding unauthorized access to the specified equipment.

3. For installation at thermal units of Electronics subscribers, the following types of devices are recommended, which are included in the State Register of Measuring Instruments: "Rise", VKT, TREM, TS-11, TS-7, SPT.

4. Requirements for installed means of heat energy metering:

4.1 Accuracy class for measuring network water flow< ± 2 %.

4.2. The minimum limit for measuring the network water flow of the metering device must be lower than the actual flow rate of the coolant.

4.3. The sheet of registration of daily parameters of heat consumption, printed from the installed heat metering stations, must contain:

The amount of heat energy consumed per day (Gcal);

Coolant consumption in the supply pipeline per day (t);

Coolant consumption in the return pipeline per day (t):

Average daily temperature of the heat carrier in the supply pipeline (С0)

Average daily temperature of the heat carrier in the return pipeline (С0);

Coolant consumption per day for feeding internal heating and ventilation systems (t);

Operating time of the heat energy metering unit (hour);

Indications of accumulators at the beginning, end of the reporting period and their difference for the reporting period;

Consumption of thermal energy;

Consumption of network water in the supply and return pipelines;

make-up water consumption;

Operating time of the device.

4.4. Provide for the transfer of information from the subscriber's thermal energy metering station via telephone wired or cellular communication channels.

PUTTING THE HEAT METERING UNIT INTO OPERATION

5. For commissioning of the heat energy metering unit and execution of the Certificate of Tolerance, it is necessary:

5.1. Availability of the "Project of the metering unit for thermal energy and coolant", agreed with Electronics.

5.2. Compliance of the installation of the metering station equipment with the Project approved by Electronics.

5.3. Availability of the Record of registration of daily parameters of heat consumption for the handed over node of the couple for a period of at least 7 days.

5.4. Availability of passport documents for the installed elements of the heat energy metering unit.

5.5. Availability of original certificates of the State verification of the elements of the metering unit.

5.6. The absence of an actual overestimation of t2 is a fact, in comparison with the temperature graph t2 graph on the thermal unit.

5.7. Absence of excess leaks of network water at this subscriber.

5.8. Absence of raw water impurities at this subscriber.

6. Additional terms:

6.1. Work on the design and installation of heat energy metering units should be carried out by a specialized organization.

6.2. Complete the node shield with connectors for connecting a portable adapter and a laptop.

6.3. Provide for the transfer of information in the project: a report for the consumed thermal energy and its current value - via the communication system in Electronics.

6.4. Acceptance of the Accounting Unit and the communication system is formalized by a single act.

7. Validity period of the "Specifications" until ______________________ 20___.

Operations Director

Reading time: 7 minutes

Heating is one of the most expensive items on your utility bill. The calculation is based on standards and tariffs - indicators established in accordance with the legislation of the Russian Federation by the executive authorities of the subject in the field of state regulation of prices. Also, the payment structure may include the volume of heat energy consumption in the event that a common house heat meter is installed in an apartment building. Let's find out in which cases installation is required, how to do it correctly and how residents will benefit.

    Appointment of a common house meter for heating

    After the Housing Code determined what is the property of tenants, their area of ​​responsibility has expanded significantly. Responsibilities for the maintenance and service of common house property fell on the shoulders of apartment owners.

    Since it is impossible to refuse to pay for general house needs, it makes sense to reduce the cost of heating residential and non-residential premises and pay only for the heat actually received.

    To measure the amount of energy consumed, a common house heat meter (ODPU) is installed. By paying for heating in an apartment building by the meter, you will be able to control energy consumption and keep track of expenses. This is not the only purpose of the ODPU installation.

    Another goal pursued is to encourage residents to save heat outside their own apartments and take good care of common property.

    If the doors and windows in the entrance are tightly closed, the heat will remain, and the residents will receive the service in full.

    It should be mentioned right away that the ODPU itself does not save anything. This is just a metering device that provides more accurate data for determining the final amount of payment for heating than the standards.

    Installing a common house heat meter is legal

    For the first time, general house meters were discussed back in 2009, when Federal Law No. 261-FZ “On Energy Saving and Increasing Energy Efficiency” was issued. In its original version, the law prescribed the mandatory installation of an ODPU in multi-storey buildings until January 1, 2012. Later this period was extended several times.

    The last change in the deadline until January 1, 2019 and until January 1, 2021 (for Crimea and Sevastopol) was enshrined in Federal Law N196-FZ of 07/26/2017.

    Thus, the law on common building meters for heating unequivocally confirms the need for their installation in apartment buildings. An exception is allowed only for dilapidated, emergency and demolished houses, as well as objects on which the installation of a meter is technically impossible due to the inconsistency of the engineering network parameters with the installation conditions of the device.

    Procedure for installing a collective heat meter

    If the centralized heat supply system has the technical ability to install a common house heat energy meter, it must be installed.

    In newly built houses, energy meters are installed before the facility is put into operation. This requirement contains the law on the installation of a common house meter dated November 23, 2009 No. 261-FZ in paragraphs 7-8 of Article 11, and paragraph 9 of Article 13 defines the area of ​​responsibility for installing an ODPU in houses where it is not available.

    In order for a house-wide metering device to appear in the house, it is necessary to go through several stages of the installation procedure.

    1. The meeting of owners of an apartment building (MKD) is the basis for the installation of heat meters for heating in an apartment building.
    2. The meeting may be initiated by the Management Company. In, ZhSK, ZhK, the meeting is held on the basis of an application from the owners, 10% of the signatures of the total number of votes are sufficient.
    3. The technical conditions for the ODPU installation, in accordance with which its design and installation will be carried out, are issued by the heat supply organization.
    4. The project for the installation and the estimate for the work is prepared by the design organization, taking into account the specific installation site and indicating the model of the device.
    5. Coordination of the project in the heat supply organization that issued the technical conditions.
    6. Acquisition of the ODPU approved by the project, necessarily with a verification mark.
    7. Installation of ODPU and putting the meter into operation.
    8. Organizations responsible for the installation

      According to Law No. 261-FZ, the obligation to install a collective heat energy meter lies with the apartment owners of a multi-storey building, who must carry out this measure on their own, choosing an equipment supplier and a contractor for the work.

      Assuming that there will be houses that are not equipped with ODPU, legislators have determined who should install heat meters in this case. So, if on July 1, 2012 there was no heat meter in the houses, the responsibility for its installation was shifted to the resource supply organization (RSO).

      In addition, the RNO is obliged to prepare proposals for equipping apartment buildings with metering devices and carry out the relevant work, which is confirmed in the letter of the Federal Antimonopoly Service of Russia dated 08.12.2011 No. AG / 45584.

      Thus, the widespread information that the management company installs meters for heating is erroneous. The task of the CC is only to:

  • bring to the attention of the owners of MKD apartments the need to install a collective heat meter;
  • organize a meeting;
  • draw up a protocol of consent.

Measures for installing the device can be carried out by organizations supplying heat energy or specialized companies that have:

  1. Qualified specialists in the staff of the company.
  2. Permission to perform the relevant type of work issued by the SRO.

How much does a common house heating meter cost

Since heat meters for heating, in accordance with Law No. 261-FZ, are the property of residents of an apartment building and they bear all the costs of their purchase and installation, the issue of the cost of the ODPU is very important. Consider what items of expenditure make up the amount of installation of a collective meter.

  1. The cost of the device. The price of a heat meter directly depends on its type and manufacturer. There are several types of heat meters:
  • tachometric - the cheapest models (6-10 thousand rubles) with a service life of 2 to 4 years;
  • vortex - a more expensive option, the average price of which is 15 thousand rubles;
  • electromagnetic - costing 15-17 thousand rubles;
  • ultrasonic - depending on the model, the price from the manufacturer ranges from 15,000 to 50,000 rubles.
  1. The cost of preparing a document containing the technical specifications of the heat supply system and developing design documentation for the metering station equipment.
  2. The price of an additional set of equipment and related materials.
  3. Installation cost: installation, electrical installation, as well as commissioning.

All costs result in a rather high amount: from 150 to 300 thousand rubles. Here it is to be paid to the residents of the house. You can do this in several ways:

  • one-time payment (mandatory for legal entities);
  • installment payment, which is provided for a period of up to 60 months and is paid in equal installments. The interest rate depends on the refinancing rate set by the Central Bank.
  • means of the overhaul fund, provided that this service is included in the list of works on common property in the MKD for the constituent entity of the Russian Federation, in accordance with the Housing Code of the Russian Federation (part 2 of article 166).

The payment mechanism is regulated by law: the amount is distributed among all apartment owners, depending on the area of ​​​​housing and the timing of depositing funds.

Take a sociological survey!

Maintenance of common house heat energy meters

Maintenance of the meter involves maintaining it in working condition. This is achieved as a result of preventive measures, such as:

  • inspection and elimination of the causes affecting the wear and tear of the control and measuring unit;
  • checking the operation of additional equipment;
  • operational maintenance and control of the metrological accuracy of measurements of the metering device;
  • weekly readings for analysis and development of recommendations for maintaining the required temperature.

If during the test a malfunction is detected, the device is dismantled, the damage is repaired and reinstalled.

Reconciliation of readings of a common house heat meter

To calculate monthly payments, accurate and timely readings are needed, which are taken from the common house meter. In accordance with Decree of the Government of the Russian Federation No. 354 dated 05/06/2011, the utility service provider is responsible for accounting for heat energy, which may be:

  • Management Company;
  • resource organization.

Results

The Law on Energy Saving obliges residents of apartment buildings to install common heat meters at their own expense, with the exception of houses that do not meet technical capabilities.

Both the UK and the RSO take part in the installation procedure of the ODPU, the former organizes, and the latter is responsible for the installation of the device. In case of failure to fulfill their obligations, companies will be fined, and residents will receive a receipt for payment for heating with a multiplier. Time will tell how expedient the compulsory installation of collective meters is, but the effect of the use of ODPU is undeniable: heating costs are reduced by up to 30%.

Lawyer. Member of the Chamber of Advocates of St. Petersburg. Experience more than 10 years. Graduated from St. Petersburg State University. I specialize in civil, family, housing, land law.

In accordance with the Federal Law "On Heat Supply", the Government of the Russian Federation decides:

1. Approve the attached Rules for the commercial accounting of thermal energy, heat carrier.

2. Federal executive authorities within 3 months to bring their regulatory legal acts in line with this resolution.

3. The Ministry of Construction and Housing and Communal Services of the Russian Federation shall approve within 2 weeks the methodology for commercial metering of thermal energy, heat carrier.

Prime Minister
Russian Federation
D. Medvedev

Rules for commercial metering of thermal energy, coolant

I. General provisions

1. These Rules establish the procedure for organizing commercial accounting of thermal energy, heat carrier, including:

A) requirements for metering devices;
b) characteristics of thermal energy, coolant to be measured for the purpose of commercial accounting of thermal energy, coolant and quality control of heat supply;
c) the procedure for determining the amount of supplied thermal energy, heat carrier for the purpose of commercial accounting of heat energy, heat carrier (including by calculation);
d) the procedure for distributing losses of thermal energy, heat carrier by heat networks in the absence of metering devices at the boundaries of adjacent heat networks.

2. The methodology for commercial metering of thermal energy, coolant is determined by the methodology approved by the Ministry of Construction and Housing and Communal Services of the Russian Federation (hereinafter referred to as the methodology).

3. The terms used in these Rules mean the following:

"commissioning of a metering station" - a procedure for checking the compliance of a heat metering station with the requirements of regulatory legal acts and project documentation, including drawing up an act of commissioning a heat metering station;

"water meter" - a measuring device designed to measure the volume (mass) of water (liquid) flowing in a pipeline through a section perpendicular to the direction of the flow velocity;

"time of operation of metering devices" - the time interval during which, based on the readings of metering devices, heat energy is recorded, as well as the measurement and registration of the mass (volume) and temperature of the coolant;

"thermal network output" - the output of thermal networks from a source of thermal energy in a certain direction;

"computer" - a component of a heat meter that receives signals from sensors and provides calculation and accumulation of data on the amount of thermal energy and coolant parameters;

"dependent connection scheme of a heat-consuming installation" - a scheme for connecting a heat-consuming installation to a heat network, in which the heat carrier from the heat network enters directly into the heat-consuming installation;

"closed water heat supply system" - a complex of technologically interconnected engineering structures designed for heat supply without taking hot water (heat carrier) from the heating network;

"measuring metering system" - a multi-channel measuring instrument, including channels for measuring thermal energy with measuring components - heat meters, as well as additional measuring channels for the mass (volume) of the coolant and its parameters - temperature and pressure;

"individual heating point" - a set of devices for connecting a heat-consuming installation to a heat network, converting the parameters of a heat carrier and distributing it by type of heat load for one building, structure or structure;

"quality of heat energy" - a set of parameters (temperatures and pressures) of the heat carrier used in the processes of production, transmission and consumption of heat energy, ensuring the suitability of the heat carrier for the operation of heat-consuming installations in accordance with their purpose;

"saturated steam" - water vapor in thermodynamic equilibrium with water in contact with it;

"independent scheme for connecting a heat-consuming installation" - a scheme for connecting a heat-consuming installation to a heat network, in which the heat carrier coming from the heat network passes through a heat exchanger installed at the heat point, where it heats the secondary heat carrier used later in the heat-consuming installation;

"malfunction of measuring instruments of the metering unit" - the state of the measuring instruments, in which the metering unit does not comply with the requirements of regulatory legal acts, regulatory and technical and (or) design (project) documentation (including due to the expiration of the verification of measuring instruments included in composition of the metering unit, violation of the established seals, as well as with work in emergency situations);

"open water heat supply system" - a complex of technologically interconnected engineering structures intended for heat supply and (or) hot water supply by taking hot water (heat carrier) from a heating network or taking hot water from hot water supply networks;

"superheated steam" - water vapor having a temperature higher than the saturation temperature at a certain pressure;

"make-up" - a heat carrier additionally supplied to the heat supply system to make up for its technological consumption and losses during the transfer of heat energy;

"metering device" - a measuring instrument, including technical devices that perform the functions of measuring, accumulating, storing and displaying information on the amount of thermal energy, as well as on the mass (volume), temperature, pressure of the coolant and the operating time of the devices;

"coolant flow rate" - the mass (volume) of the coolant that has passed through the cross section of the pipeline per unit of time;

"flow meter" - a device designed to measure the flow of a coolant;

"calculation method" - a set of organizational procedures and mathematical actions to determine the amount of thermal energy, heat carrier in the absence of metering devices or their inoperability, used in cases established by these Rules;

"cutting the temperature graph" - maintaining a constant temperature of the coolant in the heating network, regardless of the outdoor temperature;

"heat meter" - a device designed to measure the thermal energy given off by a coolant or consumed along with it, which is a single structure or consists of constituent elements - flow converters, flow meters, water meters, temperature (pressure) sensors and a calculator;

"technical operation of the metering unit" - a set of operations for the maintenance and repair of elements of the heat metering unit, ensuring the reliability of measurement results;

"metering unit" - a technical system consisting of measuring instruments and devices that provide accounting for thermal energy, mass (volume) of the coolant, as well as control and registration of coolant parameters;

"Heat carrier leak" - loss of water (steam) through leaks in process equipment, pipelines and heat-consuming installations;

"form of the measuring system of accounting" - a document drawn up in relation to the measuring system of the metering unit and reflecting, among other things, the composition of the metering unit and changes in its composition;

"functional failure" - a malfunction in the system of the metering unit or its elements, in which the accounting of thermal energy, mass (volume) of the coolant stops or becomes unreliable;

"central heating point" - a set of devices for connecting heat-consuming installations of several buildings, structures or structures to a heat network, as well as for converting the parameters of the coolant and distributing it by type of heat load.

4. Commercial metering of thermal energy, coolant is organized in order to:

A) settlements between heat supply, heat network organizations and consumers of heat energy;
b) control over the thermal and hydraulic modes of operation of heat supply systems and heat-consuming installations;
c) control over the rational use of thermal energy, coolant;
d) documentation of coolant parameters - mass (volume), temperature and pressure.

5. Commercial metering of thermal energy, coolant is carried out using metering devices that are installed at the metering point located on the border of the balance sheet, if a heat supply contract, a contract for the supply of thermal energy (capacity), a coolant or a contract for the provision of services for the transfer of thermal energy, coolant ( hereinafter referred to as the contract) no other accounting point is defined.

6. Metering units put into operation before the entry into force of these Rules can be used for commercial metering of thermal energy, coolant before the expiration of the service life of the main metering devices (flow meter, heat calculator) that are part of the metering units.

7. After 3 years from the date of entry into force of these Rules, heat meters that do not meet the requirements of these Rules cannot be used for installation in both new and existing metering units.

8. Heat supply organizations or other persons are not entitled to demand from the consumer of thermal energy the installation of devices or additional devices at the metering station that are not provided for by these Rules.

9. The heat supply organization, the heat network organization and the consumer have the right to install additional devices at the metering station to control the mode of supply and consumption of thermal energy, heat carrier, including for remote reading from the heat meter, without interfering with the implementation of commercial metering of heat energy, heat carrier and not affecting the accuracy and quality of measurements.

10. In case of installation of remote reading equipment at the metering station, access to the said system is entitled to be obtained by the heat supply (heat network) organization and the consumer in the manner and on the terms determined by the contract.

11. In the event that a single consumer of thermal energy is connected to the heat network, which departs from the source of thermal energy, and this thermal network belongs to the specified consumer of thermal energy on the basis of ownership or other legal grounds, by agreement of the parties to the contract, it is allowed to keep records of the consumed thermal energy according to the readings of the device metering installed at the metering unit of the source of thermal energy.

12. If one of the parties to the contract, which is obliged in accordance with federal laws to install a metering device, does not fulfill this obligation, the other party to the contract is obliged, in accordance with the procedure established by the legislation of the Russian Federation, to install a metering device for making payments under the contract.

13. If both parties to the contract have installed a metering device, for commercial metering of heat energy, heat carrier under the contract, the readings of the metering device that is installed on the boundary of the balance sheet are used.

If there are 2 equivalent metering stations on opposite sides of the boundary of the balance sheet, for the commercial metering of heat energy, heat carrier, the readings of the metering station are accepted, which provides accounting with a minimum error. The error in this case consists of the value of unmeasured heat losses from the boundary of the balance sheet to the metering unit and the reduced measurement error.

14. The metering devices used must comply with the requirements of the legislation of the Russian Federation on ensuring the uniformity of measurements in force at the time the metering devices are put into operation.

After the interval between verifications has expired or after the failure of metering devices or their loss, if this happened before the expiration of the interval between verifications, metering devices that do not comply with the requirements of the legislation of the Russian Federation on ensuring the uniformity of measurements are subject to verification or replacement with new metering devices.

15. Commercial metering of thermal energy, coolant is organized at all points of supply and points of acceptance.

16. Commercial metering of heat energy, heat carrier supplied to consumers of heat energy, heat carrier can be organized both by heat supply organizations, heat network organizations, and heat energy consumers.

17. The organization of commercial accounting of thermal energy, heat carrier, unless otherwise provided by the provisions of these Rules, includes:

A) obtaining technical specifications for the design of the metering unit;
b) design and installation of metering devices;
c) commissioning of the metering unit;
d) operation of metering devices, including the procedure for regularly taking readings from metering devices and using them for commercial metering of thermal energy, coolant;
e) verification, repair and replacement of metering devices.

18. Issuance of technical specifications for the installation of a metering unit (device), commissioning, sealing of metering units (devices) and participation in commissions for the acceptance of metering units (devices) is carried out without charging a fee from the consumer of thermal energy.

19. Metering units are equipped in a place as close as possible to the border of the balance sheet belonging of pipelines, taking into account the real possibilities at the facility.

20. At sources of thermal energy, metering units are installed at each outlet of the heating network.

21. The selection of thermal energy, coolant for own and economic needs of the source of thermal energy is organized up to metering stations at the outlets. In other cases, the selection of thermal energy, coolant should be carried out through separate metering units.

The coolant is withdrawn for replenishment of heat supply systems with the installation of a separate meter from the return pipeline after the flow sensor along the flow of the coolant. Pressure sensors can be installed both before the flow sensor and after it. Temperature sensors are installed after the flow sensor in the direction of the coolant flow.

22. If sections of the heating network are owned or otherwise legally owned by different persons, or if there are jumpers between heating networks owned or otherwise legally owned by different persons, metering stations must be installed on the boundary of the balance sheet.

23. Collection of information on the readings of metering devices, on the amount of delivered (received, transported) thermal energy, coolant, the amount of thermal energy as part of the supplied (received, transported) hot water, the number and duration of violations that occur in the operation of metering devices, and other information , provided for by the technical documentation, displayed by metering devices, as well as taking readings from metering devices (including using telemetric systems - remote reading systems) are carried out by the consumer or the heating network organization, unless otherwise provided by the agreement with the heat supply organization.

24. Before the end of the 2nd day of the month following the billing month, the consumer or the heat grid organization shall provide the organization that provides water supply and (or) sanitation with information about the meter readings as of the 1st day of the month following the billing month, if other terms are not established by the legislation of the Russian Federation, as well as information about the current readings of metering devices within 2 working days after receiving a request for the provision of such information from the heat supply organization. Such information is sent to the heat supply organization in any available way (postal item, fax message, telephone message, electronic message using the Internet information and telecommunication network), which allows confirming the receipt of the specified information by the heat supply organization.

If the technical characteristics of the metering devices and metering units used allow the use of telemetry systems for transmitting meter readings and there is financial and technical support for the installation of telemetry modules and telemetry software, the presentation (removal) of meter readings is carried out remotely using such telemetry systems.

25. The consumer or the heating network organization is obliged to ensure unhindered access of representatives of the heat supply organization or, at the direction of the heat supply organization, representatives of another organization to the metering stations and metering devices to verify the readings of the metering devices and verify compliance with the operating conditions of the metering station devices.

26. If during the reconciliation process a discrepancy is found between the information on the readings of the metering devices of the consumer or the heat grid organization in relation to the volume of delivered (received) thermal energy, heat carrier with the information provided by the consumer or the heat grid organization, the heat supply organization draws up an act of reconciliation of the readings of the metering devices, signed by representatives consumer or heat network organization and heat supply organization.

If the representative of the consumer or the heating network organization does not agree with the content of the act of reconciliation of readings of metering devices, the representative of the consumer or the heat network organization makes a mark "acquainted" on the act and puts down his signature. The objections of the consumer or the heating network organization are indicated in the act or sent to the heat supply organization in writing in any way that allows confirming the receipt of the document by the consumer or the heating network organization. If the representative of the consumer or the heating network organization refuses to sign the act of reconciliation of meter readings, such an act is signed by the representative of the heat supply organization with the note "the representative of the consumer or the heat network organization refused to sign."

The act of reconciliation of meter readings is the basis for the recalculation of the volume of delivered (received) thermal energy, coolant from the date of signing the act of reconciliation of meter readings until the day of signing the next act.

27. In order to control the volumes of delivered (received) thermal energy, coolant, the heat supply organization or the consumer or the heat network organization has the right to use control (parallel) meters, subject to notification of one of the parties to the contract of the other party to the contract about the use of such meters.

Control (parallel) metering devices are installed on the networks of a heat supply organization, a heat grid organization or a consumer in places that allow for commercial accounting of heat energy, a heat carrier supplied to a consumer, a heat grid organization.

If the readings of the control (parallel) metering devices and the main metering devices differ by more than the measurement error of such metering devices for a period of at least one billing month, the person who installed the control (parallel) metering device may require the other party to conduct an extraordinary accounting verification of the metering device operated by this party.

28. The readings of the control (parallel) metering device are used for the purpose of commercial metering of thermal energy, coolant for the period of malfunction, verification of the main metering device, as well as in case of violation of the deadlines for submitting meter readings.

29. Installation, replacement, operation and verification of control (parallel) metering devices are carried out in accordance with the procedures provided for the installation, replacement, operation and verification of the main metering devices.

30. The person who installed the control (parallel) metering device is obliged to provide the other party to the contract (consumer, heat network organization, heat supply organization) with unimpeded access to the control (parallel) metering devices in order to control the correct installation and operation of the control (parallel) metering device.

31. Commercial accounting of thermal energy, heat carrier by calculation is allowed in the following cases:

A) the absence of metering devices at metering points;
b) malfunction of the metering device;
c) violation of the terms established by the contract for the submission of readings from metering devices that are the property of the consumer.

32. In case of non-contractual consumption of thermal energy, heat carrier, the determination of the amount of thermal energy, heat carrier used by the consumer is carried out by calculation.

II. Requirements for metering devices

33. The metering unit is equipped with heat meters and metering devices, the types of which are included in the Federal Information Fund to ensure the uniformity of measurements.

34. The heat meter consists of flow and temperature (pressure) sensors, a calculator or a combination of them. When measuring superheated steam, a steam pressure sensor is additionally installed.

Heat meters are equipped with standard industrial protocols and can be equipped with interfaces that allow organizing remote data collection in an automatic (automated) mode. These connections must not affect the metrological characteristics of the heat meter.

If the data determined remotely and the data read directly from the heat meter do not match, the basis for determining the amount of payment is the data read directly from the heat meter.

35. The design of heat meters and metering devices that are part of heat meters ensures the restriction of access to their parts in order to prevent unauthorized adjustment and interference, which can lead to distortion of measurement results.

36. In heat meters, it is allowed to correct the internal clock of the calculator without opening the seals.

37. The heat meter calculator must have an indelible archive in which the main technical characteristics and adjustment factors of the device are entered. Archive data is displayed on the device display and (or) on a computer. The adjustment coefficients are entered into the device passport. Any changes should be archived.

Design of metering units

38. For a source of thermal energy, a project of a measuring system for a metering unit is developed on the basis of the terms of reference prepared by the owner of the source of thermal energy and agreed with the adjacent heat supply (heat network) organization in terms of compliance with the requirements of these Rules, the terms of the contract and the conditions for connecting the source of thermal energy to the heat supply system.

39. The project of the metering unit for other objects in addition to sources of thermal energy is developed on the basis of:

A) technical specifications issued by the heat supply organization at the request of the consumer;
b) the requirements of these Rules;
c) technical documentation for metering devices and measuring instruments.

40. Specifications contain:

A) the name and location of the consumer;
b) data on thermal loads for each type;
c) design parameters of the coolant at the point of delivery;
d) temperature graph of the coolant supply depending on the outdoor temperature;
e) requirements for ensuring the ability to connect the metering station to the remote reading system of the meter using standard industrial protocols and interfaces, with the exception of the requirements for installing communication facilities if the heat supply organization uses or plans to use such facilities;
f) recommendations regarding measuring instruments installed at the metering station (the heat supply organization does not have the right to impose specific types of metering devices on the consumer, but for the purpose of unification and the possibility of organizing remote collection of information from the metering station, it has the right to give recommendations).

41. The heat supply organization is obliged to issue technical specifications for the installation of a metering device within 15 working days from the date of receipt of the consumer's request.

42. If within the specified period the heat supply organization does not issue technical specifications or issues technical specifications that do not contain the information established by these Rules, the consumer has the right to independently develop a draft metering unit and install a metering device in accordance with these Rules, of which he is obliged to notify heating company.

43. In the presence of ventilation and technological heat load, the technical specifications are accompanied by a work schedule and a calculation of the power of heat-consuming installations.

44. The project of the metering station contains:

A) a copy of the heat supply agreement with the attachment of acts of delimitation of balance sheet ownership and information on the design loads for existing facilities. For newly commissioned facilities, information on design loads or connection conditions is attached;
b) a plan for connecting the consumer to the heating network;
c) a schematic diagram of a heat point with a metering unit;
d) a plan of the heating point indicating the installation locations of sensors, placement of metering devices and cable wiring diagrams;
e) electrical and wiring diagrams for connecting metering devices;
f) tuning database entered into the heat meter (including when switching to summer and winter operating modes);
g) a scheme for sealing measuring instruments and devices that are part of the metering unit, in accordance with paragraph 71 of these Rules;
h) formulas for calculating thermal energy, coolant;
i) coolant flow rate for heat-consuming installations by hours of the day in winter and summer periods;
j) for metering units in buildings (optional) - a table of daily and monthly heat consumption for heat-consuming installations;
k) forms of reporting statements of readings of metering devices;
l) wiring diagrams for the installation of flow meters, temperature sensors and pressure sensors;
m) specification of the equipment and materials used.

45. The diameter of the flowmeters is selected in accordance with the design heat loads so that the minimum and maximum flow rates of the coolant do not go beyond the normalized range of the flowmeters.

46. ​​Descent devices (descents) are provided for:

A) on the supply pipeline - after the primary coolant flow converter;
b) on the return (circulation) pipeline - up to the primary coolant flow converter.

48. The set of equipment includes mounting inserts for replacing primary coolant flow converters and flow meters.

49. The design of the metering unit installed at the consumer of thermal energy is subject to agreement with the heat supply (heat network) organization that issued the technical specifications for the installation of metering devices.

50. The consumer sends a copy of the draft metering unit to the heat supply (heat network) organization for approval. If the design of the metering unit does not comply with the provisions of clause 44 of these Rules, the heat supply (heat network) organization is obliged to send the consumer a notification of the submission of missing documents (information) within 5 working days from the date of receipt of a copy of the project of the metering unit.

In this case, the deadline for receipt of the metering unit project for approval is determined from the date of submission of the finalized project.

51. The heat supply (heat network) organization is not entitled to refuse to approve the design of the metering unit if it complies with paragraph 44 of these Rules. In case of failure to provide information on approval or comments to the metering unit project within 15 working days from the date of receipt of a copy of the metering unit project, the project is considered approved.

Commissioning of the metering unit installed on the heat source

52. Mounted metering units (measuring systems of metering units) that have undergone trial operation are subject to commissioning.

53. To commission a metering unit installed at a heat source, the owner of the heat source appoints a commission for commissioning a metering unit (hereinafter referred to as the commission) in the following composition:

A) a representative of the owner of the heat source;
b) a representative of an adjacent heat grid organization;
c) a representative of the organization that carries out the installation and commissioning of the equipment put into operation.

54. The call of the representatives specified in paragraph 53 of these Rules is carried out by the owner of the heat source no later than 10 working days before the day of the proposed acceptance by sending written notifications to the members of the commission.

55. To put the metering unit into operation, the owner of the source of heat energy submits to the commission:

A) schematic diagrams for connecting the outputs of a heat source;
b) acts of delimitation of balance sheet ownership;
c) projects of metering units approved by the heat supply (heat network) organization in the manner prescribed by these Rules;
d) factory passports of the components of the metering unit, containing technical and metrological characteristics;
e) certificates of verification of instruments and sensors to be verified, with valid verification marks;
f) the form of the measuring system of the metering unit (if such a system is available);
g) the installed system, including devices that record the parameters of the coolant;
h) a record of continuous operation of devices for 3 days.

56. When putting the metering station into operation, the following is checked:

A) compliance of the serial numbers of measuring instruments with the numbers indicated in their passports;
b) compliance of the measurement ranges of parameters allowed by the temperature schedule and the hydraulic mode of operation of heat networks with the values ​​of the specified parameters determined by the contract and the conditions for connecting to the heat supply system;
c) the quality of the installation of measuring instruments and communication lines, as well as the compliance of the installation with the requirements of technical and project documentation;
d) the presence of seals of the manufacturer or repair company and the verifier.

57. When commissioning the measuring system of the metering unit at the source of heat energy, an act of commissioning the metering unit is drawn up and the metering unit is sealed. Seals are put by representatives of the organization - the owner of the source of thermal energy and the main adjacent heat supply organization.

58. The metering unit is considered suitable for commercial metering of thermal energy, heat carrier from the date of signing the commissioning certificate.

59. If a metering station does not comply with the provisions of these Rules, the metering station is not put into operation and the commissioning report contains a complete list of identified deficiencies, indicating the paragraphs of these Rules, the provisions of which are violated, and the timing of their elimination. Such an act of commissioning is drawn up and signed by all members of the commission within 3 working days.

60. Before the start of the heating period, after the next verification or repair, the readiness of the metering unit for operation is checked, about which an act of periodic inspection of the metering unit at the heat source is drawn up in the manner prescribed by paragraphs 53 - 59 of these Rules.

Commissioning of the metering unit installed at the consumer, on adjacent heat networks and on jumpers

61. The mounted metering unit, which has undergone trial operation, is subject to commissioning.

62. Commissioning of the metering unit installed at the consumer is carried out by the commission in the following composition:

A) a representative of the heat supply organization;
b) consumer representative;
c) a representative of the organization that carried out the installation and commissioning of the metering unit being put into operation.

63. The commission is created by the owner of the accounting node.

64. To put the metering station into operation, the owner of the metering station submits to the commission a project of the metering station, agreed with the heat supply organization that issued the technical specifications and the passport of the metering station or the draft passport, which includes:

A) a diagram of pipelines (starting from the border of the balance sheet) indicating the length and diameters of pipelines, valves, instrumentation, mud collectors, drains and jumpers between pipelines;
b) certificates of verification of instruments and sensors to be verified, with valid marks of the verification officer;
c) a database of tuning parameters entered into the measuring unit or heat meter;
d) a scheme for sealing measuring instruments and equipment that is part of the metering unit, excluding unauthorized actions that violate the reliability of commercial metering of thermal energy, coolant;
e) hourly (daily) statements of continuous operation of the metering station for 3 days (for objects with hot water supply - 7 days).

65. Documents for putting the metering unit into operation are submitted to the heat supply organization for consideration at least 10 working days before the expected day of commissioning.

66. When accepting a metering station for operation, the commission checks:

A) compliance of the installation of the components of the metering unit with project documentation, technical conditions and these Rules;
b) the presence of passports, certificates of verification of measuring instruments, factory seals and brands;
c) compliance of the characteristics of measuring instruments with the characteristics specified in the passport data of the metering unit;
d) compliance of the measurement ranges of parameters allowed by the temperature schedule and the hydraulic mode of operation of heat networks with the values ​​of the specified parameters determined by the contract and the conditions for connecting to the heat supply system.

67. In the absence of comments to the metering unit, the commission signs the act of commissioning the metering unit installed at the consumer.

68. The act of commissioning a metering unit serves as the basis for conducting commercial accounting of thermal energy, heat carrier according to metering devices, quality control of thermal energy and heat consumption modes using the received measurement information from the date of its signing.

69. When signing the act on the commissioning of the metering unit, the metering unit is sealed.

70. Sealing of the metering unit is carried out:

A) a representative of the heat supply organization if the metering station belongs to the consumer;
b) a consumer representative who has a metering unit installed.

71. Places and devices for sealing the metering station are prepared in advance by the installation organization. The places of connection of primary converters, connectors of electrical communication lines, protective covers on the adjustment and adjustment devices of devices, power supply cabinets of devices and other equipment, intervention in the operation of which may lead to distortion of the measurement results, are subject to sealing.

72. If the members of the commission have comments on the metering unit and identify shortcomings that impede the normal functioning of the metering unit, this metering unit is considered unsuitable for commercial metering of heat energy, coolant.

In this case, the commission draws up an act on the identified deficiencies, which provides a complete list of the identified deficiencies and the deadlines for their elimination. The specified act is drawn up and signed by all members of the commission within 3 working days. Re-acceptance of the metering station for operation is carried out after the complete elimination of the identified violations.

73. Before each heating period and after the next verification or repair of metering devices, the readiness of the metering unit for operation is checked, about which an act of periodic inspection of the metering unit at the interface between adjacent heat networks is drawn up in the manner established by paragraphs 62 - 72 of these Rules.

Operation of the metering unit installed on the source of thermal energy

74. The owner of the heat source is responsible for the technical condition of measuring instruments and devices that are part of the metering units installed at the source of thermal energy.

75. The metering unit is considered out of order in the following cases:

A) lack of measurement results;
b) unauthorized intervention in the operation of the metering unit;
c) violation of the established seals on measuring instruments and devices that are part of the metering unit, as well as damage to electrical communication lines;
d) mechanical damage to measuring instruments and devices that are part of the metering unit;
e) the presence of tie-ins in pipelines that are not provided for by the design of the metering unit;
f) expiration of the calibration period for any of the devices (sensors);
g) work in excess of the normalized limits during most of the billing period.

76. The time of failure of the metering unit installed on the source of thermal energy is recorded in the log of meter readings.

77. The representative of the owner of the source of thermal energy is also obliged to report to the heat network organization and the unified heat supply organization data on the readings of metering devices at the time of their failure.

78. The owner of the source of heat energy is obliged to inform the consumer about the failure of the metering devices that are part of the metering unit, if the metering is carried out using these metering devices that are part of the metering unit installed on the source of heat energy, and transfer to the consumer the data of the readings of the devices at the time their failure.

79. Representatives of the heat supply organization and consumers (if metering is carried out using devices installed on the heat source) are provided with unhindered access to the metering unit and documentation related to the metering unit.

Operation of the metering unit installed by the consumer on adjacent heating networks and on jumpers

80. Within the period established by the contract, the consumer or a person authorized by him shall submit to the heat supply organization a report on heat consumption, signed by the consumer. The contract may provide that the report on heat consumption is submitted on paper, on electronic media or using dispatching tools (using an automated information and measuring system).

81. The consumer has the right to demand, and the heat supply organization is obliged to submit to him the calculation of the amount of consumed heat energy, heat carrier for the reporting period no later than 15 days after the submission of the heat consumption report.

82. If the metering station belongs to a heat supply (heat network) organization, the consumer has the right to demand copies of printouts from metering devices for the reporting period.

83. If there are reasons to doubt the reliability of meter readings, any party to the contract has the right to initiate a commission check of the functioning of the metering unit with the participation of the heat supply (heat network) organization and the consumer. The results of the commission's work are documented by an act of checking the functioning of the metering unit.

84. If disagreements arise between the parties to the agreement on the correctness of the readings of the metering station, the owner of the metering station, at the request of the other party to the contract, within 15 days from the date of the application, organizes an extraordinary verification of the metering devices that are part of the metering station, with the participation of a representative of the heat supply organization and the consumer.

85. If the correctness of the meter readings is confirmed, the costs of the extraordinary verification shall be borne by the party to the contract that requested the extraordinary verification. In case of detection of the fact of unreliability of meter readings, the costs are borne by the owner of the metering station.

86. When violations are detected in the operation of the metering unit, the amount of consumed thermal energy is determined by the calculation method from the moment the metering device that is part of the metering unit fails. The time of failure of the metering device is determined according to the data of the heat meter archive, and in their absence - from the date of submission of the last report on heat consumption.

87. The owner of the metering station is obliged to ensure:

A) unhindered access to the metering station for the party to the contract;
b) the safety of installed metering units;
c) the safety of seals on measuring instruments and devices that are part of the metering unit.

88. If the metering station is installed in a room that does not belong to the owner of the metering station on the basis of ownership or other legal grounds, the owner of the premises shall bear the obligations provided for in paragraph 87 of these Rules.

89. If any violations in the functioning of the metering station are detected, the consumer is obliged to notify the service organization and the heat supply organization within 24 hours and draw up an act signed by representatives of the consumer and the service organization. The consumer submits this act to the heat supply organization along with a report on heat consumption for the relevant period within the time period specified by the contract.

90. In case of untimely notification by the consumer about violations of the functioning of the metering unit, the calculation of the consumption of thermal energy, coolant for the reporting period is carried out by calculation.

91. At least once a year, and also after the next (extraordinary) verification or repair, the performance of the metering unit is checked, namely:

A) the presence of seals (brands) of the verifier and the heat supply organization;
b) verification validity period;
c) operability of each measurement channel;
d) compliance with the permissible measurement range for the meter of the actual values ​​of the measured parameters;
e) compliance of the characteristics of the heat meter settings with the characteristics contained in the input database.

92. The results of checking the metering unit are documented in acts signed by representatives of the heat supply organization and the consumer.

93. An assessment of the deviation of indicators of the quality of heat supply and heat consumption from the values ​​\u200b\u200bspecified in the contract is carried out on the basis of the readings of metering devices that are part of the metering unit installed at the consumer, or portable measuring instruments. The measuring instruments used must be verified. The absence of appropriate measurements serves as the basis for rejecting the consumer's claims regarding the quality of thermal energy, heat carrier.

III. Characteristics of thermal energy, heat carrier to be measured for the purpose of their commercial accounting and quality control of heat supply

94. The amount of thermal energy used, inter alia, for the purposes of hot water supply, the mass (volume) of the heat carrier, as well as the values ​​of the quality indicators of thermal energy during its release, transmission and consumption are subject to commercial accounting of thermal energy, heat carrier.

95. For the purpose of commercial accounting of thermal energy, heat carrier and quality control of heat supply, the following is measured:


b) pressure in the supply and return pipelines;
c) temperature of the heat carrier in the supply and return pipelines (return water temperature in accordance with the temperature chart);
d) coolant flow in the supply and return pipelines;
e) coolant flow in the heating and hot water supply system, including the maximum hourly flow;
f) the flow rate of the heat carrier used to make up the heat supply system, if there is a make-up pipeline.

96. For the purpose of commercial accounting of thermal energy, heat carrier and quality control of heat supply at the source of thermal energy, when steam is used as a heat carrier, the following is measured:

A) the operating time of the metering station devices in normal and abnormal modes;
b) released thermal energy per hour, day and billing period;
c) the mass (volume) of released steam and condensate returned to the heat source per hour, day and billing period;
d) temperatures of steam, condensate and cold water per hour and per day, followed by determination of their weighted average values;
e) pressure of steam, condensate per hour and per day, followed by determination of their weighted average values.

97. In open and closed heat consumption systems at the heat energy and heat carrier metering unit, using the device (s), the following are determined:

A) the mass (volume) of the coolant received through the supply pipeline and returned through the return pipeline;
b) the mass (volume) of the heat carrier received through the supply pipeline and returned through the return pipeline for each hour;
c) average hourly and average daily temperature of the coolant in the supply and return pipelines of the metering unit.

98. In open and closed heat consumption systems, the total heat load of which does not exceed 0.1 Gcal / h, at the metering station using instruments, only the operating time of the metering station devices, the mass (volume) of the received and returned coolant, as well as the mass (volume ) of the coolant used for make-up.

99. In heat consumption systems connected according to an independent scheme, the mass (volume) of the heat carrier consumed for make-up is additionally determined.

100. In open heat consumption systems, the following are additionally determined:

A) the mass (volume) of the coolant used for water intake in hot water supply systems;
b) average hourly pressure of the coolant in the supply and return pipelines of the metering unit.

101. Average hourly and average daily values ​​of the coolant parameters are determined based on the readings of instruments that record the parameters of the coolant.

102. In steam heat consumption systems at the metering station, using instruments, the following are determined:

A) the mass (volume) of the resulting steam;
b) mass (volume) of the returned condensate;
c) mass (volume) of steam produced per hour;
d) average hourly values ​​of steam temperature and pressure;
e) average hourly temperature of the returned condensate.

103. The average hourly values ​​of the coolant parameters are determined on the basis of the readings of the instruments that record these parameters.

104. In heat consumption systems connected to heat networks according to an independent scheme, the mass (volume) of condensate used for make-up is determined.

Quality control of heat supply

105. Quality control of heat supply during the supply and consumption of heat energy is carried out at the boundaries of the balance sheet between the heat supply, heat network organization and the consumer.

106. The quality of heat supply is defined as the totality of the characteristics of heat energy established by regulatory legal acts of the Russian Federation and (or) the heat supply contract, including the thermodynamic parameters of the heat carrier.

107. The following parameters characterizing the thermal and hydraulic regime of the heat supply system of heat supply and heat network organizations are subject to quality control of heat supply:


pressure in the supply and return pipelines;
the temperature of the heat carrier in the supply pipeline in accordance with the temperature schedule specified in the heat supply contract;

B) when connecting the consumer's heat-consuming installation through a central heating point or when directly connected to heating networks:

differential pressure at the outlet of the central heating point between the pressure in the supply and return pipelines;
compliance with the temperature schedule at the inlet of the heating system during the entire heating period;
pressure in the supply and circulation pipeline of hot water supply;
temperature in the supply and circulation pipeline of hot water supply;

C) when connecting the consumer's heat-consuming installation through an individual heating point:
pressure in the supply and return pipelines;
compliance with the temperature schedule at the inlet of the heating network during the entire heating period.

108. The following parameters characterizing the thermal and hydraulic regime of the consumer are subject to quality control of heat supply:

A) when connecting the heat-consuming installation of the consumer directly to the heat network:
return water temperature in accordance with the temperature schedule specified in the heat supply contract;
heat carrier consumption, including the maximum hourly consumption, determined by the heat supply agreement;
make-up water consumption, determined by the heat supply agreement;

B) when connecting the consumer's heat-consuming installation through a central heat point, an individual heat point or with direct connection to heat networks:
temperature of the heat carrier returned from the heating system in accordance with the temperature schedule;
coolant flow in the heating system;
make-up water consumption according to the heat supply contract.

109. Specific values ​​of controlled parameters are indicated in the heat supply contract.

IV. The procedure for determining the amount of supplied thermal energy, heat carrier for the purpose of their commercial accounting, including by calculation

110. The amount of thermal energy, coolant supplied by a source of thermal energy, for the purpose of their commercial accounting, is determined as the sum of the quantities of thermal energy, coolant for each pipeline (supply, return and make-up).

111. The amount of thermal energy, coolant received by the consumer is determined by the energy supply organization based on the readings of the consumer's metering station devices for the billing period.

112. If, in order to determine the amount of supplied (consumed) thermal energy, heat carrier for the purpose of their commercial accounting, it is required to measure the temperature of cold water at the source of thermal energy, it is allowed to enter the specified temperature into the calculator in the form of a constant with periodic recalculation of the amount of consumed thermal energy, taking into account the actual cold water temperature. The introduction of zero cold water temperature is allowed throughout the year.

113. The value of the actual temperature is determined:

A) for the heat carrier - by a single heat supply organization based on data on the actual average monthly values ​​of the temperature of cold water at the source of heat energy provided by the owners of heat energy sources, which are the same for all consumers of heat energy within the boundaries of the heat supply system. The frequency of recalculation is determined in the contract;

B) for hot water - by the organization operating the central heating point, based on measurements of the actual temperature of cold water in front of hot water heaters. The frequency of recalculation is determined in the contract.

114. Determination of the amount of delivered (received) thermal energy, heat carrier for the purpose of commercial accounting of thermal energy, heat carrier (including by calculation) is carried out in accordance with the methodology for commercial accounting of thermal energy, heat carrier approved by the Ministry of Construction and Housing and Communal Services of the Russian Federation (hereinafter referred to as the methodology). In accordance with the methodology, the following is carried out:

A) organization of commercial accounting at the source of thermal energy, coolant and in thermal networks;

B) determination of the amount of thermal energy, coolant for the purpose of their commercial accounting, including:

The amount of thermal energy, coolant released by the source of thermal energy, coolant;
the amount of thermal energy and mass (volume) of the coolant received by the consumer;
the amount of thermal energy, coolant consumed by the consumer during the absence of commercial metering of thermal energy, coolant according to metering devices;

C) determination of the amount of thermal energy, coolant by calculation for connection through a central heating point, individual heating point, from sources of thermal energy, coolant, as well as for other connection methods;

D) determination by calculation of the amount of thermal energy, heat carrier in case of non-contractual consumption of thermal energy;

E) determination of the distribution of losses of thermal energy, coolant;

E) during the operation of metering devices for an incomplete billing period, the adjustment of heat energy consumption by calculation for the time of absence of readings in accordance with the methodology.

115. If there are no metering devices at the metering points or the operation of metering devices for more than 15 days of the billing period, the determination of the amount of thermal energy spent on heating and ventilation is carried out by calculation and is based on the recalculation of the base indicator for the change in outdoor temperature for the entire billing period.

116. The value of the heat load specified in the heat supply contract is taken as the base indicator.

117. The recalculation of the base indicator is carried out according to the actual average daily outdoor temperature for the billing period, taken according to meteorological observations of the weather station closest to the heat consumption facility of the territorial executive body that performs the functions of providing public services in the field of hydrometeorology.

If during the period of cutting the temperature graph in the heating network at positive outdoor temperatures there is no automatic control of the heat supply to heating, and also if the temperature graph is cut during the period of low outdoor temperatures, the value of the outdoor air temperature is assumed to be equal to the temperature indicated at the beginning of the cut graphic arts. With automatic control of heat supply, the actual temperature value indicated at the beginning of the graph cutoff is taken.

118. In the event of a malfunction of metering devices, the expiration of their calibration period, including the withdrawal from operation for repair or verification for up to 15 days, the average daily amount of thermal energy, heat carrier determined by metering devices for the time regular operation in the reporting period, reduced to the calculated outdoor temperature.

119. In case of violation of the deadlines for submitting instrument readings, the amount of thermal energy, heat carrier determined by metering instruments for the previous billing period, reduced to the estimated outdoor air temperature, is taken as an average daily indicator.

If the previous settlement period falls on another heating period or there are no data for the previous period, the amount of thermal energy, heat carrier is recalculated in accordance with paragraph 121 of these Rules.

120. The amount of thermal energy, coolant spent on hot water supply, in the presence of separate metering and temporary malfunction of devices (up to 30 days), is calculated based on the actual consumption determined by metering devices for the previous period.

121. In the absence of separate accounting or inoperative state of devices for more than 30 days, the amount of thermal energy, heat carrier consumed for hot water supply is taken equal to the values ​​\u200b\u200bestablished in the heat supply contract (the amount of heat load for hot water supply).

122. When determining the amount of thermal energy, coolant, the amount of thermal energy supplied (received) in the event of emergency situations is taken into account. Emergency situations include:

A) operation of the heat meter at coolant flow rates below the minimum or above the maximum limit of the flow meter;
b) operation of the heat meter when the temperature difference of the heat carrier is below the minimum value set for the corresponding heat meter;
c) functional failure;
d) change in the direction of the heat carrier flow, if such a function is not specifically provided for in the heat meter;
e) lack of power supply to the heat meter;
f) lack of coolant.

123. The following periods of abnormal operation of metering devices should be determined in the heat meter:

A) the duration of any malfunction (accident) of measuring instruments (including a change in the direction of the coolant flow) or other devices of the metering unit that make it impossible to measure thermal energy;
b) power outage time;
c) the time of absence of water in the pipeline.

124. If the heat meter has a function for determining the time during which there is no water in the pipeline, the time of lack of water is allocated separately and the amount of heat energy for this period is not calculated. In other cases, the time of lack of water is included in the time of the emergency.

125. The amount of coolant (thermal energy) lost due to leakage is calculated in the following cases:

A) leakage, including leakage on the consumer's networks to the metering station, is identified and formalized by joint documents (bilateral acts);
b) the amount of leakage recorded by the water meter when feeding independent systems exceeds the normative one.

126. In the cases specified in paragraph 125 of these Rules, the amount of leakage is determined as the difference between the absolute values ​​of the measured values ​​without taking into account errors.

In other cases, the amount of heat carrier leakage specified in the heat supply contract is taken into account.

127. The mass of the heat carrier consumed by all consumers of thermal energy and lost in the form of a leak in the entire heat supply system from the source of heat energy is determined as the mass of the heat carrier consumed by the source of heat energy to feed all pipelines of water heat networks, minus intra-station costs for own needs during production electric energy and in the production of thermal energy, for the production and economic needs of the objects of this source and intra-station technological losses by pipelines, units and apparatuses within the boundaries of the source.

V. The procedure for the distribution of losses of thermal energy, coolant between heating networks in the absence of metering devices at the boundaries of adjacent heating networks

128. The distribution of losses of thermal energy, coolant, as well as the amount of thermal energy, coolant transferred between the heat networks of heat supply organizations and heat network organizations in the absence of metering devices at the borders of adjacent parts of heat networks, is calculated as follows:

A) in relation to heat energy transferred (received) at the border of the balance sheet of adjacent heat networks, the calculation is based on the balance of the amount of heat released into the heat network and consumed by heat-consuming consumer installations (for all owner organizations and (or) other legal owners of adjacent heating networks) for all sections of pipelines at the boundary (boundaries) of the balance belonging of adjacent sections of the heating network, taking into account the losses of thermal energy associated with emergency leaks and technological losses (pressure testing, testing), losses through damaged thermal insulation in adjacent heating networks, which are formalized by acts , norms of technological losses during the transmission of thermal energy and losses exceeding the approved values ​​(excess losses);

B) in relation to the heat carrier transferred at the border of the balance belonging of adjacent heat networks, the calculation is based on the balance of the amount of heat carrier released into the heat network and consumed by heat-consuming installations of consumers, taking into account the losses of the heat carrier associated with emergency leaks of the heat carrier, executed acts, standards for technological losses at transfer of thermal energy, approved in the prescribed manner, and losses exceeding the approved values ​​(excess).

129. The distribution of excess losses of thermal energy, heat carrier between adjacent heat networks is carried out in quantities proportional to the values ​​​​of the approved standards of technological losses and losses of thermal energy, taking into account emergency leaks of the heat carrier through damaged thermal insulation.

130. In case of transmission of heat energy, heat carrier through a section of the heat network owned by the consumer, when distributing losses of heat energy, heat carrier and excess losses of heat energy, heat carrier, these heat networks are considered as adjacent heat networks.